Technicial Specifications
Minimum Rating | 65 kVA |
Maximum Rating | 65 kVA |
Emissions/Fuel Strategy | Non Regulated |
Voltage | 220 to 415 Volts |
Frequency | 50 Hz |
Speed | 1500 rpm |
Duty Cycle | Standby, Prime |
Engine Model | Cat® C3.3 |
Bore | 105 mm |
Stroke | 127 mm |
Displacement | 3.3 l |
Compression Ratio | 17.25:1 |
Aspiration | Turbocharged |
Fuel System | Inline |
Governor Type | Mechanical |
Length - Maximum | 1925 mm |
Width - Maximum | 1120 mm |
Height - Maximum | 1361 mm |
Dry Weight - Genset (maximum) | 874 kg |
Advantages and Features
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
M-Frame Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
GCCP Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 55°C (131°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
Fully prototype tested with certified torsional vibration analysis availableOne Safe Source
- Components used in the generator set are selected based on seamless design integration to provide the optimum performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
World Wide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Standard Equipment
-
Control panel
- GCCP Control panel
-
Alternator and Alternator attachments
- 12 Leads
- IP23 Protection
- Voltage regulator (single phase sensing)
- Tower panel, IP22, bottom cable entry
- Segregated low voltage (AC/DC) wiring panel
- Circuit breaker, IEC, 3 Pole, mounted in tower panel
-
Governing system
- Mechanical governor
-
Cooling system
- Radiator and cooling fan with guards
- Coolant drain line with valve
- Fan drive, battery charging alternator drive
- Caterpillar extended life coolant
-
Air inlet system
- Air cleaner; light duty with disposable element
-
Exhaust system
- Stub pipe, gaskets, raincap & SAE exhaust flange
- Industrial silencer
-
Fuel system
- Standard open set fuel tank/base
-
Lube system
- Lubricating oil
- Oil drain line with valve
-
Mounting system
- Captive linear vibration isolators
- Lifting provision and drag points
- Termination points for coolant and lube oil drain lines
-
Starting/charging system
- 12V Battery with rack & cables
-
General
- Engine and alternator pre-paint, Caterpillar yellow
Optional Equipment
-
Control panel
- GCCP Control panel
- Earth fault and earth leakage
- Emergency E-Stop with security key
- 4 Pole Circuit breaker
- Voltage and speed adjust potentiometer
-
Alternator and Alternator Attachments
- LC Frame alternator
- LC/M Frame alternator
- Space heater
- Permanent magnet excitation (PMG)
- Automatic voltage regulator
-
Enclosures
- Level 1 and Level 2 sound attenuated enclosures
- Single point lifting frame
- Rental pack
- SBOX - CEE form sockets
-
Alarms and Shutdowns
- Common alarm
- Overload shutdown
- Low coolant level shutdown
- Low coolant temperature alarm
- Low fuel level alarm and shutdown
- High fuel level alarm
-
Engine
- Electronic governor
- Jacket water heater
- Battery charger
-
Fuel system
- Bunded base tank sized for a minimum of 12 hours running with 110% spill protection
-
Exhaust system
- Residential silencer 25 dBA
-
Certification
- Certificate of Conformance
- EAC Certification
-
Extended service coverage
- 3, 4, 5 and 10 Years